System Screen Errors

The table provides a list of C-more panel SSC (System Screen) errors.

See the C-More5 Error Code Lookup Tool for error codes and explanations.

Error Code Error Message Description

SSC-100

Please enter the year from %1 to %2.

Enter a valid value for the Year.

SSC-101

Date is incorrect.

Enter a valid value for the Date.

SSC-130

Input value is invalid. Please input all octets from the first octet to the fourth octet. The value of each octet should be 0~255.

See message on panel.

SSC-131

Input value is invalid. Please input all octets from the first octet to the fourth octet. The value of each octet should be 0~255.

See message on panel.

SSC-132

The combination of "Static" for "IP Address" and"Obtain DNS Server Address from DHCP" for "DNS Server"cannot be set.

Select either Static or DHCP for both IP Address and DNS server.

SSC-133

These are the same network address(%1/%2)

Network addresses must be different for each Ethernet Port. Example: Eth Port 1: 192.168.12.1/16, Eth Port 2: 192.168.10.100/16. Both have Network address 192.168.0.0 (/16 = Subnet Mask 255.255.0.0).

SSC-134

Invalid IP Address.

The input IP address is a link-local address (169.254 series). Choose a different IP address that is not a link-local address.

SSC-135

The Default  Gateway Network address does not match any of the Port IP Addresses.

The Default Gateway Network Address must match one of the Ethernet Port IP addresses. Example: Default Gateway: 192.168.0.1, Port 1: 192.168.0.25/24 (matches), Port 2: 172.31.60.25/24, Port 3: 10.11.10.5/25.

SSC-136

An unexpected error has occurred. Please reopen the system screen again. (Code: %1)

SSC-300

%1 does not have enough free space. Please use a %2 with more space.

The backup destination device does not have enough space. Choose another device.

SSC-301

An exception error has occurred. Unable to execute.

The folder /home/CM5/EA/WSUpdatePanel does not exist. Perform a firmware update to correct this.

SSC-302

Invalid storage is selected. %1

The backup destination is not set. Back out of screen and select destination device again or try a different device.

SSC-303

Invalid data area is selected.

Select a valid backup target.

SSC-304

Another process is in progress. Please try again after a while.

Try again in a few minutes. Another process is using memory.

SSC-305

Cannot run in safe mode.

Try again in a few minutes. Another process is using memory. Cycle power and update firmware if possible. If problem continues, there may be a hardware defect.

SSC-306

Backup Failed.%1

Backup to device failed. Try again. If problem continues, reformat the backup device or try a different device. Make sure power is not interrupted.

SSC-310

Backed up Firmware Support Panel:%1 Restore Panel Type:%2 Cannot restore because the panel type is not supported by the firmware.

The target panel does not match the backup panel model. See the table below for combinations that are not allowed.

SSC-311

The Restore Project is configured to boot from SD1. Please Insert SD1.

Insert SD Card into SD1 slot and try again.

SSC-312

Project version: %1 Current Panel version: %2 Cannot restore because the Project version does not match the Panel Firmware version.

The backup does not contain the firmware version, so the project file in the backup must match the panel firmware. Update the panel firmware to match the backup file version using the CM5-PGMSW software or backup the file again, making sure to select to backup both firmware and project.

SSC-313

Cannot restore because the project size exceeds the %1 memory available.

Clear panel memory and try again. Make sure the panel you are restoring to is the correct model with the same amount of source panel memory.

SSC-314

An exception error has occurred. Unable to execute.

The folder /home/CM5/EA/WSUpdatePanel does not exist. Perform a firmware update to correct this.

SSC-315

Invalid storage is selected. %1

The restore destination is not set. Back out of screen and select destination device again or try a different device.

SSC-316

Invalid data area is selected.

Select a valid restore device.

SSC-317

Another process is in progress. Please try again after a while.

Try again in a few minutes. Another process is using memory.

SSC-318

Cannot run in safe mode.

Try again in a few minutes. Another process is using memory. Cycle power, update firmware if possible. If problem continues, there may be a hardware defect.

SSC-319

Restore Failed..%1

Restoration from device failed. Try again. If the problem continues, try a different device. Make sure power is not interrupted.

SSC-320

Invalid storage is selected. %1

Select a valid target device and files.

SSC-321

Restoration is not possible because the Panel Type is different. Restore Project Type : %1 Current Panel Type: %2

Backup file does not match the restore panel. Choose the correct restore panel model.

These backup and restore combinations will not work.

From To

CM5-T4W

CM5-T10

CM5-T12W

CM5-T15W

CM5-T22W

CM5-T7W

CM5-T10

CM5-T12W

CM5-T15W

CM5-T22W

CM5-T10

CM5-T4W

CM5-T7W

CM5-T12W

CM5-T4W

CM5-T7W

CM5-T15W

CM5-T4W

CM5-T7W

CM5-T22W

CM5-T4W

CM5-T7W

CM471