Connect to C-More with Modbus TCP
This procedure will walk through setting up the ModbusTCP mapping with the XEM CPU as a server and a C-More EA9 HMI as the client.
Some programming is required for transferring STRING values between the XEM CPU and C-More HMI.
Supported Data Types
XG5000 Data Type | C-More Data Type Equivalent |
---|---|
BOOL | Discrete |
INT | Signed int 16 |
UINT | Unsigned int 16 |
DINT | Signed int 32 |
UDINT | Unsigned int 32 |
REAL | Floating PT 32 |
WORD | Unsigned int 16 |
DWORD | Unsigned int 32 |
STRING | Ascii String |
Procedures
Follow the referenced procedures below to connect to C-More via Modbus TCP.
You can also download an example program here:
LP203