STRING data over Modbus

XG5000 supports up to 31 characters in a STRING variable.

  • Each ASCII character needs to be handled as a byte in Modbus communication.

  • 32 bytes of Modbus data should be allocated for each STRING variable.

XG5000 Variable Declarations

Variable Kind Variable Type Address
VAR STRING_FROM_HMI STRING %MW1616
VAR STRING_TO_HMI STRING %MD308

 

C-More Tag Database

Assign 32 characters to the tag Data Count.

Device Name Tag Name Data Type Address Data Count
DEV002 STRING_FROM_PLC Ascii String 30017 32
DEV002 STRING_TO_PLC Ascii String 40017 32

 

 

LP203-3