Runtime Errors
See the C-More5 Error Code Lookup Tool for error codes and explanations.
Runtime Errors
Error Code Causes and Possible Solutions
RTE-004
| Possible Cause | Solution |
|---|---|
|
The external storage device (USB, SD, and so on) has not completed the data write. |
Complete the data write before you start a new process. |
|
The SYS xxx EJECT tag stopped the process during the data write. |
Put the memory device back in and try again. |
RTE-042
| Possible Cause | Solution |
|---|---|
|
Incorrect send-to email address in the Address Book database. |
Make sure the send-to address is correct. |
|
Incorrect send-from email address in the Panel Settings Email Client tab. |
Make sure that the email address and password are correct in the Panel Settings Email Client tab. |
| The email server is specified by URL but no DNS server is configured. | Open the panel network dialog, select the Ethernet Port settings and confirm a DNS server is configured |
| No internet access | From a PC with confirmed internet access ping the C-more's IP address |
|
Email server blocks send-from or IP address. |
Examine the server requirements and limitations. |
|
Email server requires an SSL connection. |
Examine the server requirements and limitations. |
RTE-130
| Possible Cause | Solution |
|---|---|
|
The project exists on the SD card inserted in SD1 and when you remove the SD card, the project is no longer on the panel. |
Insert the SD card that contains the project into SD1 again. Versions after 6.14 show a message that the project stops if you eject the SD card. You can cancel the action, and the project is not changed. If you remove the SD card without the SYS SD1 Eject tag, a message shows that the project is stopped. |
|
The project exists on the SD card inserted in SD1 and you want to restore the project to the panel, but you remove the SD card. |
Runtime Errors
CM413