Mitsubishi Melsec FX PLC Addressing

Topic: CM260

This addressing table applies to the Mitsubishi FX-1N(C)/2N(C)/3U(C) CPU Protocol and the Mitsubishi FX Series Protocol as noted.

Memory Type Address Range Bit Specification Description Read/Write Type Data Type
X 0 to 177 (Octal Number) — Input Read Only Discrete
Y 0 to 177 (Octal Number) — Output Read Only Discrete
T 0 to 255 (Decimal Number) — Timer Present Elapsed Time Read Only Word
T .0 to.255 (Decimal Number) — Timer Output Read Only Discrete
C 0 to 199 (Decimal Number) — Counter Present value Read Only Word
C 200 to 255 (Decimal Number) — Counter Present value Read Only Discrete
C .0 to.255 (Decimal Number) — Counter Output Read Only Word
D* 0 to 7999 (Decimal Number) — Data Register R/W Word
D 8000 to 8255 (Decimal Number) — Data Register Read Only Word
S 0 to 999 (Decimal Number) — State R/W Discrete
M** 0 to 3071 (Decimal Number) — Relay R/W Discrete
M 8000 to 8255 (Decimal Number) — Relay Read Only Discrete

* D - Range for Mitsubishi FX Series CPU drivers is 0-999

** M - Range for Mitsubishi FX Series CPU drivers is 0-1535

Related Topics Link IconRelated Topics